Spirax Sarco LP10-4 Liquid Level Sensor
Brand authorization
- Rapid response service
- Professional team support
- Flexible return and exchange policy
Description
The Spirax Sarco LP10-4 Liquid Level Controller is used in conjunction with the Spirax Sarco LC1350 Liquid Level Controller for on/off level control and alarming of steam boilers, tanks, or other vessels. 4-probe sensors are suitable for use where a 3-lamp "electronic display" level/alarm indicator is installed. The body of the sensor is grounded through a threaded connection, and when used in concrete or plastic tanks, a probe can be grounded or a separate ground rod or plate can be supplied.The 4 probes are removable and can be cut to the required length prior to installation (the probes must be ordered separately), and are immersed in a conductive liquid to form an electrical circuit loop, which will signal to the controller when the level is lower than the probes and the resistance is increased.
Probe Length
The probes are available in lengths of 1000mm, with a maximum length of 2095mm when two probes are connected.
Pressure/Temperature Limits
pressure rating | PN40 |
---|---|
Maximum pressure | 32 bar g (464 psi g) |
highest temperature | 239 °C (462 °F) |
Maximum ambient temperature | 70 °C (158 °F) |
minimum ambient temperature | -20 °C (-4 °F) |
Technical Parameters
Protection level | IP54 |
---|---|
Maximum Cable Length (Sensor to Controller) | 30 m (98 ft) |
Maximum sensing temperature | 2095 mm (82.5") |
Minimum Sensing Depth | 75 mm (3") |
Minimum conductivity (when used with LC1350) | 1S/cm @ 25℃ |
material (that sth is made of)
Item | Part | material (that sth is made of) |
---|---|---|
1 | Protection level | Austenitic stainless steel BS EN 10088-3 (1.4306) |
2 | extend one's head (out or into) | Austenitic Stainless Steel Type 316/ 316L |
3 | Probe Insulation Sleeve | PFA (Per Fluor Alkoxy) |
4 | Lower part of wire cover | PPS (Polyphenyline sulphide) |
5 | Upper part of wire cover | PPS (Polyphenyline sulphide) |
6 | Gland support pads | flexible thermoplastic |
7 | Cable gland | polyacrylate |
8 | Probe Stator | PEEK (Polyaryletherketone) Grade 450G |
Safety, Installation and Maintenance
This document does not contain sufficient information for safe installation, as detailed in the Installation and Maintenance Guide supplied with the product.
WARNING: If this product is exposed to excessive heat, the plastic contained in its material will emit toxic gases.
INSTALLATION: LP10-4 is designed to be installed on a BSPRP1 (1" BSP tapered) or 1" NPT screwed flange or cover plate, the thread specification must be specified at the time of installation. For installation in boilers or tanks where there is a strongly disturbed condition, it is recommended to use a protection pipe with a minimum nominal bore diameter of 80mm. Installation outdoors should be weatherproof.
Connection: The connection of the LP10-4 is simple and straightforward, the connectors can be supplied as spare parts, the terminals are marked in different colors for easy differentiation, and the disconnection can be done by opening the wire unit without removing the cable gland.
MAINTENANCE: Although the boiler water level control needs to be tested regularly, this product requires no special maintenance.
Product Description
Austenitic stainless steel body and inductor probe with PFA probe insulation for boilers up to 32 bar g (239°C).
Ordering Instructions
Example: 1 - Spirax Sarco LP10-4 sensor (BSP), probe length 1000mm.
Spare parts available
LP10-4 wire connectors: includes 6 flat connectors and 2 round connectors.
LP10-4 Probe Mounting Kit: Includes one 1-probe connector, one locking screw female and two screw head stators.
weights
1.15kg