The Spirax Sarco LC2650 Level Controller for electrically conductive fluids provides level switching or regulating control of boilers, tanks and vessels, with an operating limit of 32 bar @ 239°C and two alarm channels with separate high or low alarm settings. The minimum conductivity applicable to the controller is 5us/cm or 5ppm (using LP20 and PA20).

The front panel is equipped with an LCD display and five buttons.The LCD display shows operational information in run mode and also shows the level fluctuation trend over a set time period. In run mode, frequently used data is displayed in several consecutive screens. The test menu has a diagnostic function to measure inputs and also to set outputs from the front panel. All commissioning parameters are password protected to prevent unwanted or incorrect settings.

The product can communicate with neighboring products via infrared bus, can be designated as master or slave, and is available in panel, DIN rail, or base plate mounting.

Main features

  • Adjust or switch control boiler water level using capacitive sensors.
  • Points can be changed.
  • Unitary, binary or ternary control.
  • An LCD graphic display and five buttons.
  • Graphical display of status, PV percentage, alarms and trend graphs.
  • Infrared communication.
  • EIA 485/Modbus communication.
  • UL and TUV certified.

accreditation

  • The LC2650 complies with the EMC Directive 2017/30/EU and its requirements and is suitable for use in heavy industrial environments with a detailed EMC assessment, reference number UK Supply BH LC2650 2008.
  • Complies with the Low Voltage Directive and meets the safety requirements of the standard EN 61010-1:2001 for electrical equipment used in measurement, control and laboratories.
  • Type-tested as level controllers in accordance with standards Vd TÜV Water Control Devices 100 (07:2006), UL Listed (open).

appliance

  • On/Off operation: Pump on/off control, 2 alarm outputs, 4 - 20mA level output (isolated), solenoid valve on/off control is also available instead of pump.
  • Regulatory control: Control valve control is by valve motor drive or 4 - 20mA control signal, 2 alarm outputs, 4 - 20mA level output (isolated).
  • Binary or ternary modulating control: Control valve control by valve motor drive or 4 - 20mA control signal, 2 alarm outputs, 4 - 20mA level output (isolated), steam flow meter feedback signal, feedwater feedforward signal.

input function

The LC2650 compares the input signal with the user's set point and changes the output signal to control the water level in the boiler or tank.

exports

The product control signals can be connected to pumps or regulating valves, and also provides relay outputs for high and low alarms, isolated 0 - 20mA or 4 - 20mA re-outputs, and parameters can be transmitted via RS485/MODBUS communication.

Other features

Additional filters are used to increase the damping effect in fluctuating conditions.

Technical Parameters

sports event particulars
power supply Supply voltage: 110 - 240 VAC, 50/60HZ
Power consumption: 7.5W (max)
matrix Indoor use only
Maximum altitude: 2000 m (6562 ft) above sea level.
Ambient temperature range: 0 - 55 °C
Maximum relative humidity: 80% at 31 °C, linearly decreasing to 50% at 40 °C
Overvoltage category: III
Contamination Class: 2 (when supplied), 3 (when mounted in a box) - Minimum IP54 or UL50 / NEMA Type 3, 3S, 4, 4X, 6, 6P or 13
Sealing rating (front panel only): NEMA Type 4 hose only (certified by UL) and IP65 compliance (certified by TRAC Global)
electrical safety EN 61010-1 UL61010-1, 3rd Edition, 2012 - 05
LVD (security) -
EMC Immunization/emission: CAN/CSA-C22.2 No. 61010-1, 3rd Edition, 2012 - 05 for heavy industrial locations
housings Material: Polycarbonate 294
Front Panel Material: (Blue) Silicone Rubber, 60shore
solder Tin/lead (60/40%)
Power and Signal Connectors Terminals: Plug-in terminals with screw connectors. Note: Use only terminals supplied by Spirax Sarco, otherwise safety and approvals will be reduced.
Cable size: 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG).
Strip length: 5 - 6 mm at high temperatures
Liquid Level Sensor Type of shielding: Shielding
Cables/wires for feedback, steam and water flow meters Number of cores: 3 cores (LP20/PA20), 2 or 3 (4 - 20mA transmitter)
Size: 1 - 1.5 mm² (18 - 16 AWG)
Maximum length: 100 m (328 ft)
Recommended type: Prysmian (Pirelli) FP200, Delta Crompton Firetuf OHLS
0/4 - 20 mA output cable/wire Type: twisted pair
Type of shielding: Shielding
Number of cores: 1
Size: 0.23 - 1 mm² (24 - 18 AWG)
Maximum length: 100 m (328 ft)
RS485 communication cable/wiring Type: EIA RS485 twisted-pair cable
Type of shielding: Shielding
Logarithm: 2 or 3
Size: 0.23 mm² (24 AWG)
Maximum length: 1200 m (4000 ft)
Recommended type: Alpha 6413 or 6414. can be used with LAN Cat 5 or Cat 5E ScTP (shielded), FTP (thin slice), or STP Alpha 6413 or 6414 but limited to 600 meters
Input of technical data Level Voltage: Minimum 0Vdc or 1V (over-range selectable), Maximum 6Vdc (Absolute Maximum = 7Vdc ), Input Impedance 28 kΩ, Accuracy 5% FSD operating range, Repeatability 2.5% FSD operating range, Resolution 14 bit (approx. 0.15 mV), Sampling time 260 Hz, Minimum Current 0 mA, Maximum Current 20 mA Input impedance 110 Ω, repeatability 2.5% FSD operating range, resolution 14 bits (approx. 1uA), sampling time 260 Hz
Level 'out of' range alarm - Voltage: min alarm level 1 Vdc, max alarm level > 6.5 Vdc, max recovery level < 6 Vdc
Level 'out of' range alarm - Current: min alarm level 4 mA, max alarm level > 21 mA, max recovery level < 20 mA
24 Vdc power supply: 32 Vdc max (no load, open), 25 mA max, 10 mV swing, full load
4 - 20 mA: Minimum current 0 mA, maximum current 22 mA, open loop voltage 19 Vdc (max), resolution 1% FSD, maximum output load 500 ohms, insulation 100 V, output ratio 10/sec.
exports Contacts: 2 × single-pole changeover relay (SPCO)
Rated voltage (max): 250 Vac
Relays: Resistive Load 3 amp @ 250 Vac, Inductive Load 1 amp @ 250 Vac, AC Motor Load ¼ HP (2.9 amp) @ 250 Vac, 1 / 10 HP (3 amp) @ 120 Vac, Pilot Work Load C300 (2.5 amp) - Control Circuits/Coils
Electrical life (action): 3 x 10⁵ or greater, depending on load
Mechanical life (action): 30 x 10⁶
RS485 Physical layer: RS485 4-wire full-duplex or 2-wire half-duplex
Protocol layer: Modbus RTU format
Insulation: 60 Vac/dc
Receiving unit load: (256 devices - maximum)
Output rate: up to 10 fps
infrared communication Physical layer: IrDA
Baud rate: 38400
Range: 10 cm
Working angle: 15 °
Eye Safety Information: Abstract: EN 60825-12 : 2007 Safety of laser products - Not exceeding the Class 1 emission limit (AEL)

Safety information, Installation and maintenance

WARNING: This document does not contain sufficient information to safely install the product. The product operates at hazardous voltages, refer to the Installation and Maintenance Guide supplied with the product before installing the product.
Note: Ensure that there is no condensation inside the product before installing and connecting the power cord. The product can be DIN rail, base plate board or panel mounted and is supplied with an instrument bezel. The product must be mounted in a suitable industrial control panel or fire rated enclosure to provide crash and environmental protection, a minimum of IP54 (EN 60529 standard) or Types 3, 3S, 4, 4X, 6, 6P & 13 (UL50/NEMA 250) is required, Spirax Sarco offers suitable plastic and metal boxes.

  • Do not install outdoors without additional weather protection.
  • Do not attempt to open the product - it is sealed and has no replaceable parts or internal switches.
  • Do not block infrared rays between products.
    In the UK, the IEE specification (BS 7671) is to be followed, and in other regions, the appropriate protocols are to be followed. All wiring materials and processes must comply with the appropriate EN and IEC standards.
    No special service, preventive maintenance or product inspection is required. Boiler water level controls and alarms need to be tested and checked and general guidance is given in Health and Safety Directives BG01 and INDG436.

weights

550g

How to Order

Example: 1 x Spirax Sarco LC2650 level controller.