Description
Spirax Sarco FT14 Float Steam Trap (Threaded Connection), made of ductile iron, with built-in automatic air venting device and threaded connection, can be serviced in-line without disassembling the piping.
Available Models
Available types |
SKU |
Spirax Sarco FT14-4.5 1 1/4" Threads |
1478000 |
Spirax Sarco FT14-10 1 1/4" Thread |
1478100 |
Spirax Sarco FT14-14 1 1/4" thread |
1478200 |
Spirax Sarco FT14-4.5 1 1/2" Threads |
666000 |
Spirax Sarco FT14-10 1 1/2" Thread |
666100 |
Spirax Sarco FT14-14 1 1/2" Thread |
666200 |
Spirax Sarco FT14-4.5 2" Threads |
668000 |
Spirax Sarco FT14-10 2" Threaded |
668100 |
Spirax Sarco FT14-14 2" Threaded |
668200 |
Other Options
Available types |
connection method |
FT14(R-L) |
Horizontal connection from right to left |
FT14(L-R) |
Horizontal connection from left to right |
FT14(V) |
Flow down vertical connection |
Available types |
specificities |
FT14C |
In addition to an air vent, a steam lock release device (SLR) is included to prevent steam lock in the system, with the letter "C" after the model name. |
FT14X |
With built-in filter |
Liquid bladder: Using the BP99/32 liquid bladder, it can be applied to superheated vapors with a superheat of 150°C @ 0 bar g and 50°C @ 32 bar g.
Standard: Complies with the European Pressure Equipment Directive 97/23/EC.
Certificates: Manufacturer's test reports are available; if certificates are required, please specify when ordering.
Sizes and pipe connections: ½", ¾" and 1" Screwed, BSP or NPT.
Scope of work
parameters |
particulars |
Valve body design conditions |
PN16 |
PMA Maximum Allowable Pressure |
16 bar g@100°C |
TMA Maximum Allowable Temperature |
250°C@13 bar g |
Minimum permissible temperature |
-10°C |
PMO Maximum Working Pressure under Saturated Steam |
14 bar g |
TMO Maximum Operating Temperature |
250°C@13 bar g |
Minimum working temperature |
0°C |
ΔPMX Maximum Differential Pressure (FT14-4.5) |
4.5 bar |
ΔPMX Maximum Differential Pressure (FT14-10) |
10 bar |
ΔPMX Maximum Differential Pressure (FT14-14) |
14 bar |
Design maximum cold hydraulic test pressure |
24 bar g |
material (that sth is made of)
Item |
Part |
material (that sth is made of) |
6 |
Main Valve / Air Vent Valve Seat Gasket |
Stainless steel (BS 1449 409 S19) |
7 |
Main valve assembly screws |
Stainless steel (BS 6105 CI A2-70) |
8 |
Float Rod Mechanism |
Stainless steel (BS 1449 304 S16) |
9 |
Air Vent Valve Assembly |
stainless steels |
10 |
Pivot bracket |
Stainless steel (BS 1449 304 S16) |
11 |
fulcrum pin |
stainless steels |
12 |
SLR device |
Stainless steel (BS 970 303 S21) |
13 |
SLR Gasket |
Stainless steel (BS 1449 304 S16) |
14 |
SLR Seal |
plumbago |
15 |
Anti-erosion guide (1" only) |
Stainless steel (BS 970 431 S29) |
16 |
Main valve spring (1" only) |
Stainless steel (BS 2056 302 S26) |
1 |
valve body |
Ductile iron (DIN 1693 GGG 40) |
2 |
Bonnet bolts |
Steel (BS 3692 Gr.8.8) |
3 |
Bonnet Gasket |
Reinforced flake graphite |
4 |
bonnets |
Ductile iron (DIN 1693 GGG 40) |
5 |
Main valve seat |
Stainless steel (BS 970 431 S29) |
weights
caliber |
Weight (kg) |
½" |
2.9 |
¾" |
2.9 |
1" |
4.0 |
SAFETY INFORMATION, INSTALLATION, AND MAINTENANCE: Refer to the Installation and Maintenance Guide (IM-S02-13) supplied with the product for detailed information. Install so that the direction of fluid flow is in the same direction as indicated by the arrow on the valve body, and ensure that the float arm is positioned horizontally to ensure that the float is free to rise and fall vertically, and that the direction of flow can be changed in the field, if desired.
Disposal: This product can be recycled and does not cause environmental problems when disposed of properly.
Ordering Instructions: Examples: 1 - Spirax Sarco ½" FT4-4.5(R-L) Float Steam Trap, BSP Threaded Connection with Air Vent.